Guide
3-Circuit Track: Selecting the Phase
The rail is up, the fitting is in, the supply is live — and the fitting is dark. On three-circuit track this is usually not a fault. It is a selector set to the wrong position.
First, the thing worth knowing
A three-circuit rail is not one circuit. It carries three separately switched live conductors inside a single profile, plus neutral. Any fitting on that rail has to be told which of the three it should draw from — and that is what the selector on the fitting does.
One rail, three circuits
The rail runs three live conductors down its length. Each is switched independently, so one run of track can carry three lighting scenes instead of one — without installing a second rail.
The selector decides which of the three the fitting draws from. Here it is set to L1, so it ignores L2 and L3.
The selector itself
On the fittings we supply, the selector has four positions: three phases and an off position. It is a small rotary switch on the fitting body, usually reachable without taking the fitting off the rail.
Four positions: three phases and off. Match the number to the circuit you want that fitting on.
How to set it
1. Switch the supply off
Isolate the circuit before touching the fitting. This is not optional — the selector is a mains switch.
2. Decide the scheme
Agree which fittings belong on which circuit. In retail this is usually base lighting, accent and display — one circuit each.
3. Set and test one circuit at a time
Set each fitting's selector, then switch on one circuit only and confirm exactly the intended fittings light. Repeat for the next.
If a fitting will not light
Work through this in order. In our experience the first item resolves most of these calls.
| Check | What you are looking for |
|---|---|
| 1. Selector position | The most common cause. The fitting is set to a phase that is not switched on, or is on 0 / OFF. Turn the selector to another phase and retest. |
| 2. Which circuit is live | Switch the circuits one at a time and confirm which fittings respond. This tells you whether the selector or the supply is the problem. |
| 3. Seating on the rail | The fitting must be fully seated so the contacts engage. Lift it out and reseat it — a partial fit can look correct and still not make contact. |
| 4. Feed and connectors | Check the live-end feed and any joints. Confirm the feed is on the circuit you think it is. |
| 5. Then suspect the fitting | Move the fitting to a position known to work. If it lights there, the fitting is fine and the problem is in the rail run. |
Safety notes
Isolate before working
Switch off the supply or disconnect the feed before any work on the rail or the fitting. Do not modify the product.
Indoor, dry locations
These fittings are for dry indoor use. Do not install them where they will be exposed to water or sustained moisture.
Mounting surface
Install on normal, non-flammable surfaces only, and respect the specified ambient temperature range for the model.
Light source
The LED light source is not user-replaceable and can only be replaced by the manufacturer. Do not attempt to open the sealed optical chamber.
Always follow the installation instructions supplied with the specific model, and have mains work carried out by a qualified electrician. If you are unsure, isolate the circuit and ask.
Next step
Send us a photo and we will tell you what you have
A photo of the rail end and of the selector on the fitting is usually enough for us to confirm the system and the correct position. Tell us the market and the project and we will quote the matching parts.
Drawings and site photos can follow by WhatsApp or email. No upload needed to start.
Quick enquiry
Five fields. We reply within one business day.
Questions buyers ask
Frequently asked questions
When do I need 3-phase track lighting?
When you want to switch or dim several independent lighting groups from one rail (zones, scenes, or balancing load across phases). Single-circuit (2-wire) track cannot separate groups.